Features:
- Solid State Relay Assemblies rated to 25A/pole @ 40° C (100% duty cycle)

- Available in 1, 2 & 3 Pole configurations

- Relays approved to the following: UL, CSA, VDE and CE

- Zero cross switching standard

- Compact heat sink design for space limited applications

- Finger safe cover standard

- Phase angle & time proportioning control optional

OUTPUT SPECIFICATIONS AC Control
 
HBC-25AS
HBC-25HAS
HBC-625AS
HBC-50AS
HBC-50HAS
HBC-650HAS
Operating Voltage  (47-63 Hz) [Vrms]
24-280
48-530
24-280
48-530
48-530
48-660
Load Current Range [Arms]
.04-15
.04-15
.04-15
.04-25
.04-25
.04-25
Transient Overvoltage [Vpk]
600
1200
1200
600
1200
1200
Max. Surge Current, (16.6ms) (Apk)
250
250
250
625
625
625
Max. On-State Voltage Drop  [Vpk]
1.6
1.7
1.7
1.6
1.7
1.7
Max. Turn-on Time (mS)
10
10
10
10
10
10
Max. Turn-off Time (mS)
40
40
40
40
40
40
Max.I²t for fusing  (8.3mS)
260
260
620
1620
1620
1620
Max. Off-State Leakage Current [mArms]
10
10
5
10
10
5
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS
Control Voltage Range [Vrms]
90-280
90-280
90-280
90-280
90-280
90-280
Max. Turn-on Voltage [Vrms]
90
90
90
90
90
90
Min. Turn-off Voltage [Vrms]
10
10
10
10
10
10
Nominal Input Impedance [Ohms]
60K
60K
60K
60K
60K
60K
Typical Input Current
2mA @ 120Vrms, 4mA @ 240Vrms
OUTPUT SPECIFICATIONS
DC Control
 
HBC-25DS
HBC-25HDS
HBC-6250DS
HBC-50DS
HBC-50HDS
HBC-650HDS
Operating Voltage  (47-63 Hz) [Vrms]
24-280
48-530
24-660
48-280
48-530
48-660
Load Current Range [Arms]
.04-15
.04-15
.04-15
.04-25
.04-25
.04-25
Transient Overvoltage [Vpk]
600
1200
1200
600
625
1200
Max. Surge Current, (16.6ms) (Apk)
250
250
250
625
625
625
Max. On-State Voltage Drop  [Vpk]
1.6
1.7
1.7
1.6
1.7
1.7
Max. Turn-on and Turn-off Time
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
Max.I²t for fusing  (8.3mS)
260
260
260
1620
1620
1620
Max. Off-State Leakage Current [mArms]
10
10
5
10
10
5
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS
Control Voltage Range [Vdc
3-32
3-32
3-32
3-32
3-32
3-32
Max. Turn-on Voltage [Vdc]
3.0
3.0
3.0
3.0
3.0
3.0
Min. Turn-off Voltage [Vdc]
1.0
1.0
1.0
1.0
1.0
1.0
Nominal Input Impedance [Ohms]
1500
See *
See *
1500
See *
See *
Typical Input Current
2.0mA *
2.0mA *
3.4mA @ 5Vdc, 20mA @ 28Vdc
2.0mA *
2.0mA *
*  Input circuitry incorporates active current limiter
Power Controller to 40A - A Series

Features:
- Solid State Relay Assemblies rated to 40 A/pole @ 40° C (100% duty cycle)

- Available in 1, 2 & 3 Pole configurations

- Relays approved to the following: UL, CSA, VDE and CE

- Zero cross switching standard

- Finger safe cover standard

OUTPUT SPECIFICATIONS AC Control
HBC-25AA
HBC-25HAA
HBC-50AA
HBC-50HAA
HBC-90HAA
HBC-690HAA
Operating Voltage  (47-63 Hz) [Vrms]
24-280
48-530
24-280
48-530
48-530
48-660
Load Current Range [Arms]
.04-20
.04-20
.04-30
.04-30
.04-40
.04-40
Transient Overvoltage [Vpk]
600
1200
600
1200
1200
1200
Max. Surge Current, (16.6ms) (Apk)
250
250
625
625
1200
1200
Max. On-State Voltage Drop  [Vpk]
1.6
1.7
1.6
1.7
1.7
1.7
Max. Turn-on Time (mS)
10
10
10
10
10
10
Max. Turn-off Time (mS)
40
40
40
40
40
40
Max.I²t for fusing  (8.3mS)
260
260
1620
1620
6000
6000
Max. Off-State Leakage Current [mArms]
10
10
10
10
10
5
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS
Control Voltage Range [Vrms]
90-280
90-280
90-280
90-280
90-280
90-280
Max. Turn-on Voltage [Vrms]
90
90
90
90
90
90
Min. Turn-off Voltage [Vrms]
10
10
10
10
10
10
Nominal Input Impedance [Ohms]
60K
60K
60K
60K
60K
60K
Typical Input Current
2mA @ 120Vrms, 4mA @ 240Vrms
OUTPUT SPECIFICATIONS
DC Control
 
HBC-25DA
HBC-25HDA
HBC-50DA
HBC-50HDA
HBC-90HDA
HBC-690HDA
Operating Voltage  (47-63 Hz) [Vrms]
24-280
48-530
24-280
48-530
48-530
48-660
Load Current Range [Arms]
.04-20
.04-20
.04-30
.04-30
.04-40
.04-40
Transient Overvoltage [Vpk]
600
1200
600
1200
1200
1200
Max. Surge Current, (16.6ms) (Apk)
250
250
625
625
1200
1200
Max. On-State Voltage Drop  [Vpk]
1.6
1.7
1.6
1.7
1.7
1.7
Max. Turn-on and Turn-off Time
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
Max.I²t for fusing  (8.3mS)
260
260
1620
1620
6000
6000
Max. Off-State Leakage Current [mArms]
10
10
10
10
10
5
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS
Control Voltage Range [Vdc
3-32
3-32
3-32
3-32
3-32
3-32
Max. Turn-on Voltage [Vdc]
3.0
3.0
3.0
3.0
3.0
3.0
Min. Turn-off Voltage [Vdc]
1.0
1.0
1.0
1.0
1.0
1.0
Nominal Input Impedance [Ohms]
1500
See *
1500
See *
See *
See *
Typical Input Current
3.4mA @ 5Vdc, 20mA @ 28Vdc
2.0mA *
3.4mA @ 5Vdc, 20mA @ 28Vdc
2.0mA *
2.0mA *
2.0mA *
*  Input circuitry incorporates active current limiter
Power Controller to 50A - L Series

Features:
- Solid State Relay Assemblies rated to 40 A/pole @ 40° C (100% duty cycle)

- Available in 1, 2 & 3 Pole configurations

- Relays approved to the following: UL, CSA, VDE and CE

- Zero cross switching standard

- Phase angle - time proportioning control optional

- Finger safe cover standard

OUTPUT SPECIFICATIONS AC DC
 
HBC-90HAL
HBC-690HAL
HBC-90HDL
HBC-690HDL
Operating Voltage  (47-63 Hz) [Vrms]
48-530
48-660
48-530
48-660
Load Current Range [Arms]
.04-50
.04-50
.04-50
.04-50
Transient Overvoltage [Vpk]
1200
1200
1200
1200
Max. Surge Current, (16.6ms) [Apk]
1200
1200
1200
1200
Max. On-State Voltage Drop  [Vpk]
1.7
1.7
1.7
1.7
Max. Turn-on Time
10.0mS
10.0mS
1/2 cycle
1/2 cycle
Max. Turn-off Time
40.0mS
40.0mS
1/2 cycle
1/2 cycle
Max.I²t for fusing  (8.3mS)
6000
6000
6000
6000
Max. Off-State Leakage Current [mArms]
10
5
10
5
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS
Control Voltage Range
90-280Vrms
90-280Vrms
3-32Vdc
3-32Vdc
Max. Turn-on Voltage
90Vrms
90Vrms
3.0Vdc
3.0Vdc
Min. Turn-off Voltage
10Vrms
10Vrms
1.0Vdc
1.0Vdc
Nominal Input Impedance [Ohms]
60K
60K
See Note *
See Note *
Typical Input Current
2mA @ 120Vrms, 4mA @ 240Vrms
2.0 mA *
* Input circuitry incorporates active current limiter.
Power Controller to 70A - K Series

Features:
- Solid State Relay Assemblies rated to 70 A/pole @ 40° C (100% duty cycle)

- Available in 1, & 2 Pole configurations

- Relays approved to the following: UL, CSA, VDE and CE

- Zero cross switching standard

- Phase angle - time proportioning control optional

- Finger safe cover standard

OUTPUT SPECIFICATIONS AC DC
 
HBC-
HBC-
HBC-
HBC-
HBC-
HBC-
 
90HAXK
690HAXK
125HAXK
90HDXK
690HDXK
125HDXK
Operating Voltage  (47-63 Hz) [Vrms]
48-530
48-660
48-530
48-530
48-660
48-530
Load Current Range [Arms]
.04-60
.04-60
.04-70
.04-60
.04-60
.04-70
Transient Overvoltage [Vpk]
1200
1200
1200
1200
1200
1200
Max. Surge Current, (16.6ms) [Apk]
1200
1200
1750
1200
1200
1750
Max. On-State Voltage Drop  [Vpk]
1.7
1.7
1.7
1.7
1.7
1.7
Max. Turn-on Time
10.0mS
10.0mS
10.0mS
1/2 cycle
1/2 cycle
10.0mS
Max. Turn-off Time
40.0mS
40.0mS
40.0mS
1/2 cycle
1/2 cycle
40.0mS
Max.I²t for fusing  (8.3mS)
6000
6000
12,700
6000
6000
12,700
Max. Off-State Leakage Current [mArms]
10
5
10
10
5
10
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS
Control Voltage Range
90-280Vrms
90-280Vrms
90-280Vrms
3-32Vdc
3-32Vdc
3-32Vdc
Max. Turn-on Voltage
90Vrms
90Vrms
90Vrms
3.0Vdc
3.0Vdc
3.0Vdc
Min. Turn-off Voltage
10Vrms
10Vrms
10Vrms
1.0Vdc
1.0Vdc
1.0Vdc
Nominal Input Impedance [Ohms]
60K Ohms
60K Ohms
60K Ohms
See Note *
See Note *
1500 **
Typical Input Current
2mA @ 120Vrms, 4mA @ 240Vrms
2.0 mA *
2.0 mA *
3.4mA @ 5Vdc, 20mA @ 28Vdc **
* Input circuitry incorporates active current limiter.
** Input circuitry for 480V models incorporates active current limiter with 2mA typical input current.
Power Controller to 40A - 3 Phase K Series
 
 

Features:
- Solid State Relay Assemblies rated to 40 A/pole @ 40° C (100% duty cycle)

- Available in 2, & 3 Pole configurations

- Relays approved to the following: UL, CSA, VDE and CE

- Zero cross switching standard

- Two or three legs controlled

- Voltage transient protection standard on 3 leg models

- LED standard on 3 leg models

- Finger safe cover standard

OUTPUT SPECIFICATIONS AC Control DC Control
 
HBC-T50AK
HBC-90HAK-2
HBC-T50DK
HBC-90HDK-2
 
3 Phase / 3 Pole
3 Phase / 2 Pole
3 Phase / 3 Pole
3 Phase / 2 Pole
Operating Voltage  (47-63 Hz) [Vrms]
48-530
48-530
48-530
48-530
Load Current Range [Arms]
0.1-30 / pole
0.1-40 / pole
0.1-30 / pole
0.1-40 / pole
Transient Overvoltage [Vpk]
1200
1200
1200
1200
Max. Surge Current, (16.6ms) [Apk]
625
1200
625
1200
Max. On-State Voltage Drop  [Vpk]
1.6
1.7
1.6
1.7
Max. Turn-on Time
10.0mS
10.0mS
1/2 cycle
1/2 cycle
Max. Turn-off Time
40.0mS
40.0mS
1/2 cycle
1/2 cycle
Max.I²t for fusing  (8.3mS)
1620
6000
1620
6000
Max. Off-State Leakage Current [mArms]
10
10
10
10
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS
Control Voltage Range
90-280Vrms (60Hz)
90-280Vrms (60Hz)
3-32Vdc
3-32Vdc
Max. Turn-on Voltage
90Vrms
90Vrms
3.0Vdc
3.0Vdc
Min. Turn-off Voltage
10Vrms
10Vrms
1.0Vdc
1.0Vdc
Nominal Input Impedance [Ohms]
54.8K
60K
450
See *
Typical Input Current
2.2mA @ 120Vrms, 4.4mA @ 240Vrms
2mA @ 120Vrms, 4mA @ 240Vrms
10mA @ 5Vdc
2.0mA *
* Input circuitry incorporates active current limiter.
Power Controller to 80A - N Series

Features:
- Solid State Relay Assemblies rated to 80A/pole @ 40° C (100% duty cycle)

- Available in 1 & 2 Pole configurations

- Relays approved to the following: UL, CSA, VDE and CE

- Zero cross switching standard

- Finger safe cover standard

- Phase angle & time proportioning control optional

OUTPUT SPECIFICATIONS AC Control
 
HBC-50AN
HBC-50HAN
HBC-90HAN
HBC-125HAN
Operating Voltage  (47-63 Hz) [Vrms]
24-280
48-530
48-530
48-530
Load Current Range [Arms]
.04-45
.04-45
.04-70
.04-80
Transient Overvoltage [Vpk]
600
1200
1200
1200
Max. Surge Current, (16.6ms) [Apk]
625
625
1200
1750
Max. On-State Voltage Drop  [Vpk]
1.6
1.7
1.7
1.7
Max. Turn-on Time
10.0mS
10.0mS
10.0mS
10.0mS
Max. Turn-off Time
40.0mS
40.0mS
40.0mS
40.0mS
Max.I²t for fusing  (8.3mS) [A²sec]
1620
1620
6000
12,700
Max. Off-State Leakage Current [mArms]
10
10
10
10
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS
Control Voltage Range
90-280Vrms
90-280Vrms
90-280Vrms
90-280Vrms
Max. Turn-on Voltage
90Vrms
90Vrms
90Vrms
90Vrms
Min. Turn-off Voltage
10Vrms
10Vrms
10Vrms
10Vrms
Nominal Input Impedance
60K Ohms
60K Ohms
60K Ohms
60K Ohms
Typical Input Current
2mA @ 120Vrms, 4mA @ 240Vrms
OUTPUT SPECIFICATIONS DC Control
 
HBC-50DN
HBC-50HDN
HBC-90HDN
HBC-125HDN
Operating Voltage  (47-63 Hz) [Vrms]
24-280
48-530
48-530
48-530
Load Current Range [Arms]
.04-45
.04-45
.04-70
.04-80
Transient Overvoltage [Vpk]
600
1200
1200
1200
Max. Surge Current, (16.6ms) [Apk]
625
625
1200
1750
Max. On-State Voltage Drop  [Vpk]
1.6
1.7
1.7
1.7
Max. Turn-on Time
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
Max. Turn-off Time
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
Max.I²t for fusing  (8.3mS) [A²sec]
1620
1620
6000
12,700
Max. Off-State Leakage Current [mArms]
10
10
10
10
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS
Control Voltage Range
3-32Vdc
3-32Vdc
3-32Vdc
3-32Vdc
Max. Turn-on Voltage
3.0Vdc
3.0Vdc
3.0Vdc
3.0Vdc
Min. Turn-off Voltage
1.0Vdc
1.0Vdc
1.0Vdc
1.0Vdc
Nominal Input Impedance
1500 Ohms
See Note *
See Note *
1500 **
Typical Input Current
3.4mA @ 5Vdc, 20mA @ 28Vdc
2.0 mA *
2.0 mA *
3.4mA @ 5Vdc, 20mA @ 28Vdc **
*Input circuitry incorporates active current limiter
** Input circuitry for 480V models incorporates active current limiter with 2mA typical input current.
Power Controller to 100A - G Series

Features:
- Solid State Relay Assemblies rated to 100A/pole @ 40° C (100% duty cycle)

- Available in 1, 2, & 3 Pole configurations

- Relays approved to the following: UL, CSA, VDE and CE

- Zero cross switching standard

- Panel mount & finger safe cover standard

- Phase angle & time proportioning control optional

INPUT SPECIFICATIONS AC DC
Part #
HBC-90HAG
HBC-690HAG
HBC-125HAG
HBC-90HDG
HBC-690HDG
HBC-125HDG
Control Voltage Range 90-280Vrms 90-280Vrms 90-280Vrms 3-32Vdc 3-32Vdc 3-32Vdc
Max. Turn-on Voltage 90Vrms 90Vrms 90Vrms 3.0Vdc 3.0Vdc 3.0Vdc
Min. Turn-off Voltage 10Vrms 10Vrms 10Vrms 1.0Vdc 1.0Vdc 1.0Vdc
Nominal Input Impedance [Ohms] 60K 60K 60K Ohms See Note * See Note * See Note *
Typical Input Current 2mA @ 120Vrms, 4mA @ 240Vrms 2.0 mA * 2.0 mA * 3.4mA @ 5Vdc, 20mA @ 28Vdc **
             
OUTPUT SPECIFICATIONS            
Operating Voltage  (47-63 Hz) [Vrms] 48-530 48-660 48-530 48-530 48-660 48-530
Load Current Range [Arms] .04-80 .04-80 .04-100 .04-80 .04-80 .04-100
Transient Overvoltage [Vpk] 1200 1200 1200 1200 1200 1200
Max. Surge Current, (16.6ms) [Apk] 1200 1200 1750 1200 1200 1750
Max. On-State Voltage Drop  [Vpk] 1.7 1.7 1.7 1.7 1.7 1.7
Max. Turn-on Time 10.0mS 10.0mS 10.0mS 1/2 cycle 1/2 cycle 1/2 cycle
Max. Turn-off Time 40.0mS 40.0mS 40.0mS 1/2 cycle 1/2 cycle 1/2 cycle
Max.I²t for fusing  (8.3mS) 6000 6000 12,700 6000 6000 12,700
Max. Off-State Leakage Current [mArms] 10 5 10 10 5 10
Power Factor  (Min.) with Max. Load 0.5 0.5 0.5 0.5 0.5 0.5
Power Controller to 80A - F Series

Features:
- Solid State Relay Assemblies rated to 80A/pole @ 40° C (100% duty cycle)

- Replaces 80A 3 pole mercury contactors

- Zero cross switching standard

- Ball bearing fan standard; 50/60 hz

- 90° C over-temp cutout switch standard

- Relays & Fan: UL, CSA, VDE and CE

- Transient voltage supression standard

- 600VAC available

OUTPUT SPECIFICATIONS AC Control DC Control
 
HBC-90AF2
HBC-90AF3
HBC-90DF2
HBC-90DF3
 
FAN OPTION (Add letter of Fan to end of above part #)
B-120VAC Fan
C - 240VAC Fan
I - 24VDC Fan
(EX:  HBC-90AF2B - Denotes 3 Phase, 2 Pole, w/120VAC Fan)
 
 
3 Phase / 2 Pole
3 Phase / 3 Pole
3 Phase / 2 Pole
3 Phase / 3 Pole
Operating Voltage  (47-63 Hz) [Vrms]
48-530
48-530
48-530
48-530
Load Current Range [Arms]
.04-80
.04-80
.04-80
.04-80
Transient Overvoltage [Vpk]
1200
1200
1200
1200
Max. Surge Current, (16.6ms) [Apk]
1200
1200
1200
1200
Max. On-State Voltage Drop  [Vpk]
1.7
1.7
1.7
1.7
Max. Turn-on Time
10.0mS
10.0mS
1/2 cycle
1/2 cycle
Max. Turn-off Time
40.0mS
40.0mS
1/2 cycle
1/2 cycle
Max.I²t for fusing  (8.3mS)
6000
6000
12700
12700
Max. Off-State Leakage Current [mArms]
10
10
10
10
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS  
Control Voltage Range 90-280Vrms (60Hz) 3-32Vdc
Max. Turn-on Voltage 90Vrms 3.0Vdc
Min. Turn-off Voltage 10Vrms 1.0Vdc
Nominal Input Impedance [Ohms] 60K See *
Typical Input Current 2.2mA @ 120Vrms, 4.4mA @ 240Vrms 2.0mA *
*  Input circuitry incorporates active current limiter
Power Controller to 100A - F Series

Features:
- Solid State Relay Assemblies rated to 100 A/pole @ 40° C (100% duty cycle)

- Replaces 100A 3 pole mercury contactors

- Zero cross switching standard

- Ball bearing fan standard; 50/60 hz

- 90° C over-temp cutout switch standard

- Relays & Fan: UL, CSA, VDE and CE

- Transient voltage supression standard

- 600VAC available

OUTPUT SPECIFICATIONS AC Control DC Control
 
HBC-125AF2
HBC-125AF3
HBC-125DF2
HBC-125DF3
 
FAN OPTION (Add letter of Fan to end of above part #)
B-120VAC Fan
C - 240VAC Fan
I - 24VDC Fan
(EX:  HBC-125AF2B - Denotes 3 Phase, 2 Pole, w/120VAC Fan)
 
 
3 Phase / 2 Pole
3 Phase / 3 Pole
3 Phase / 2 Pole
3 Phase / 3 Pole
Operating Voltage  (47-63 Hz) [Vrms]
48-530
48-530
48-530
48-530
Load Current Range [Arms]
.04-100
.04-100
.04-100
.04-100
Transient Overvoltage [Vpk]
1200
1200
1200
1200
Max. Surge Current, (16.6ms) [Apk]
1750
1750
1750
1750
Max. On-State Voltage Drop  [Vpk]
1.7
1.7
1.7
1.7
Max. Turn-on Time
10.0mS
10.0mS
1/2 cycle
1/2 cycle
Max. Turn-off Time
40.0mS
40.0mS
1/2 cycle
1/2 cycle
Max.I²t for fusing  (8.3mS)
12700
12700
12700
12700
Max. Off-State Leakage Current [mArms]
10
10
10
10
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS  
Control Voltage Range 90-280Vrms (60Hz) 3-32Vdc
Max. Turn-on Voltage 90Vrms 3.0Vdc
Min. Turn-off Voltage 10Vrms 1.0Vdc
Nominal Input Impedance [Ohms] 60K See *
Typical Input Current 2.2mA @ 120Vrms, 4.4mA @ 240Vrms 2.0mA *
*  Input circuitry incorporates active current limiter
Dual Power Controller to 40A - Dual Series

Features:
- Solid State Relay Assemblies rated to 40A @ 40° C (100% duty cycle)

- Two independent AC Relays in one package

- Available in 2, 4, & 6Pole configurations

- Zero voltage switching standard

- Standard relays approved to the following: UL, CSA, and CE

- Fast-on terminals standard

OUTPUT SPECIFICATIONS DC
 
HBC-D40HDA
HBC-D40HEA
Operating Voltage  (47-63 Hz) [Vrms]
48-530
48-530
Load Current Range [Arms]
.15-40 / pole (40A total)
.15-40 / pole (40A total)
Transient Overvoltage [Vpk]
1200
1200
Max. Surge Current, (16.6ms) (Apk)
625
625
Max. On-State Voltage Drop  [Vpk]
1.6
1.6
Max. Turn-on and Turn-off Time
1/2 cycle
1/2 cycle
Max.I²t for fusing  (8.3mS)
1620
1620
Max. Off-State Leakage Current [mArms]
10
10
Power Factor  (Min.) with Max. Load
0.5
0.5
INPUT SPECIFICATIONS
Control Voltage Range [Vdc]
4-15
4-15
Max. Turn-on Voltage [Vdc]
4.0
4.0
Min. Turn-off Voltage [Vdc]
1.0
1.0
Nominal Input Impedance [Ohms]
240
240
Typical Input Current
13mA @ 5Vdc
13ma @ 24Vdc