Power Controller to 25A
- S Series |
|
Features:
- Solid State Relay Assemblies rated to
25A/pole @ 40° C (100% duty cycle)
- Available in 1, 2 & 3 Pole configurations
- Relays approved to the following: UL,
CSA, VDE and CE
- Zero cross switching standard
- Compact heat sink design for space limited applications
- Finger safe cover standard
- Phase angle & time proportioning control
optional |
| OUTPUT SPECIFICATIONS |
AC Control |
| |
HBC-25AS
|
HBC-25HAS
|
HBC-625AS
|
HBC-50AS
|
HBC-50HAS
|
HBC-650HAS
|
| Operating Voltage (47-63 Hz) [Vrms] |
24-280 |
48-530 |
24-280 |
48-530 |
48-530 |
48-660 |
| Load Current Range [Arms] |
.04-15 |
.04-15 |
.04-15 |
.04-25 |
.04-25 |
.04-25 |
| Transient Overvoltage [Vpk] |
600 |
1200 |
1200 |
600 |
1200 |
1200 |
| Max. Surge Current, (16.6ms) (Apk) |
250 |
250 |
250 |
625 |
625 |
625 |
| Max. On-State Voltage Drop [Vpk] |
1.6 |
1.7 |
1.7 |
1.6 |
1.7 |
1.7 |
| Max. Turn-on Time (mS) |
10 |
10 |
10 |
10 |
10 |
10 |
| Max. Turn-off Time (mS) |
40 |
40 |
40 |
40 |
40 |
40 |
| Max.I²t for fusing (8.3mS) |
260 |
260 |
620 |
1620 |
1620 |
1620 |
| Max. Off-State Leakage Current [mArms] |
10 |
10 |
5 |
10 |
10 |
5 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
| Control Voltage Range [Vrms] |
90-280 |
90-280 |
90-280 |
90-280 |
90-280 |
90-280 |
| Max. Turn-on Voltage [Vrms] |
90 |
90 |
90 |
90 |
90 |
90 |
| Min. Turn-off Voltage [Vrms] |
10 |
10 |
10 |
10 |
10 |
10 |
| Nominal Input Impedance [Ohms] |
60K |
60K |
60K |
60K |
60K |
60K |
| Typical Input Current |
2mA @ 120Vrms, 4mA @ 240Vrms |
|
| OUTPUT SPECIFICATIONS |
DC Control |
| |
HBC-25DS
|
HBC-25HDS
|
HBC-6250DS
|
HBC-50DS
|
HBC-50HDS
|
HBC-650HDS
|
| Operating Voltage (47-63 Hz) [Vrms] |
24-280 |
48-530 |
24-660 |
48-280 |
48-530 |
48-660 |
| Load Current Range [Arms] |
.04-15 |
.04-15 |
.04-15 |
.04-25 |
.04-25 |
.04-25 |
| Transient Overvoltage [Vpk] |
600 |
1200 |
1200 |
600 |
625 |
1200 |
| Max. Surge Current, (16.6ms) (Apk) |
250 |
250 |
250 |
625 |
625 |
625 |
| Max. On-State Voltage Drop [Vpk] |
1.6 |
1.7 |
1.7 |
1.6 |
1.7 |
1.7 |
| Max. Turn-on and Turn-off Time |
1/2 cycle |
1/2 cycle |
1/2 cycle |
1/2 cycle |
1/2 cycle |
1/2 cycle |
| Max.I²t for fusing (8.3mS) |
260 |
260 |
260 |
1620 |
1620 |
1620 |
| Max. Off-State Leakage Current [mArms] |
10 |
10 |
5 |
10 |
10 |
5 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
| Control Voltage Range [Vdc |
3-32 |
3-32 |
3-32 |
3-32 |
3-32 |
3-32 |
| Max. Turn-on Voltage [Vdc] |
3.0 |
3.0 |
3.0 |
3.0 |
3.0 |
3.0 |
| Min. Turn-off Voltage [Vdc] |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
| Nominal Input Impedance [Ohms] |
1500 |
See * |
See * |
1500 |
See * |
See * |
| Typical Input Current |
|
2.0mA * |
2.0mA * |
3.4mA @ 5Vdc, 20mA @ 28Vdc |
2.0mA * |
2.0mA * |
| * Input circuitry incorporates active current limiter |
|
|
|
Power Controller to 40A
- A Series |
|
Features:
- Solid State Relay Assemblies rated to
40 A/pole @ 40° C (100% duty cycle)
- Available in 1, 2 & 3 Pole configurations
- Relays approved to the following: UL,
CSA, VDE and CE
- Zero cross switching standard
- Finger safe cover standard |
| OUTPUT SPECIFICATIONS |
AC Control |
HBC-25AA |
HBC-25HAA |
HBC-50AA |
HBC-50HAA |
HBC-90HAA |
HBC-690HAA |
| Operating Voltage (47-63 Hz) [Vrms] |
24-280 |
48-530 |
24-280 |
48-530 |
48-530 |
48-660 |
| Load Current Range [Arms] |
.04-20 |
.04-20 |
.04-30 |
.04-30 |
.04-40 |
.04-40 |
| Transient Overvoltage [Vpk] |
600 |
1200 |
600 |
1200 |
1200 |
1200 |
| Max. Surge Current, (16.6ms) (Apk) |
250 |
250 |
625 |
625 |
1200 |
1200 |
| Max. On-State Voltage Drop [Vpk] |
1.6 |
1.7 |
1.6 |
1.7 |
1.7 |
1.7 |
| Max. Turn-on Time (mS) |
10 |
10 |
10 |
10 |
10 |
10 |
| Max. Turn-off Time (mS) |
40 |
40 |
40 |
40 |
40 |
40 |
| Max.I²t for fusing (8.3mS) |
260 |
260 |
1620 |
1620 |
6000 |
6000 |
| Max. Off-State Leakage Current [mArms] |
10 |
10 |
10 |
10 |
10 |
5 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
| Control Voltage Range [Vrms] |
90-280 |
90-280 |
90-280 |
90-280 |
90-280 |
90-280 |
| Max. Turn-on Voltage [Vrms] |
90 |
90 |
90 |
90 |
90 |
90 |
| Min. Turn-off Voltage [Vrms] |
10 |
10 |
10 |
10 |
10 |
10 |
| Nominal Input Impedance [Ohms] |
60K |
60K |
60K |
60K |
60K |
60K |
| Typical Input Current |
2mA @ 120Vrms, 4mA @ 240Vrms |
|
| OUTPUT SPECIFICATIONS |
DC Control |
| |
HBC-25DA |
HBC-25HDA |
HBC-50DA |
HBC-50HDA |
HBC-90HDA |
HBC-690HDA |
| Operating Voltage (47-63 Hz) [Vrms] |
24-280 |
48-530 |
24-280 |
48-530 |
48-530 |
48-660 |
| Load Current Range [Arms] |
.04-20 |
.04-20 |
.04-30 |
.04-30 |
.04-40 |
.04-40 |
| Transient Overvoltage [Vpk] |
600 |
1200 |
600 |
1200 |
1200 |
1200 |
| Max. Surge Current, (16.6ms) (Apk) |
250 |
250 |
625 |
625 |
1200 |
1200 |
| Max. On-State Voltage Drop [Vpk] |
1.6 |
1.7 |
1.6 |
1.7 |
1.7 |
1.7 |
| Max. Turn-on and Turn-off Time |
1/2 cycle |
1/2 cycle |
1/2 cycle |
1/2 cycle |
1/2 cycle |
1/2 cycle |
| Max.I²t for fusing (8.3mS) |
260 |
260 |
1620 |
1620 |
6000 |
6000 |
| Max. Off-State Leakage Current [mArms] |
10 |
10 |
10 |
10 |
10 |
5 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
|
|
|
|
|
| Control Voltage Range [Vdc |
3-32 |
3-32 |
3-32 |
3-32 |
3-32 |
3-32 |
| Max. Turn-on Voltage [Vdc] |
3.0 |
3.0 |
3.0 |
3.0 |
3.0 |
3.0 |
| Min. Turn-off Voltage [Vdc] |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
| Nominal Input Impedance [Ohms] |
1500 |
See * |
1500 |
See * |
See * |
See * |
| Typical Input Current |
3.4mA @ 5Vdc, 20mA @ 28Vdc |
2.0mA * |
3.4mA @ 5Vdc, 20mA @ 28Vdc |
2.0mA * |
2.0mA * |
2.0mA * |
| * Input circuitry incorporates active current limiter |
|
|
|
Power Controller to 50A
- L Series |
|
Features:
- Solid State Relay Assemblies rated to
40 A/pole @ 40° C (100% duty cycle)
- Available in 1, 2 & 3 Pole configurations
- Relays approved to the following: UL,
CSA, VDE and CE
- Zero cross switching standard
- Phase angle - time proportioning control
optional
- Finger safe cover standard |
| OUTPUT SPECIFICATIONS |
AC |
DC |
| |
HBC-90HAL |
HBC-690HAL |
HBC-90HDL |
HBC-690HDL |
| Operating Voltage (47-63 Hz) [Vrms] |
48-530 |
48-660 |
48-530 |
48-660 |
| Load Current Range [Arms] |
.04-50 |
.04-50 |
.04-50 |
.04-50 |
| Transient Overvoltage [Vpk] |
1200 |
1200 |
1200 |
1200 |
| Max. Surge Current, (16.6ms) [Apk] |
1200 |
1200 |
1200 |
1200 |
| Max. On-State Voltage Drop [Vpk] |
1.7 |
1.7 |
1.7 |
1.7 |
| Max. Turn-on Time |
10.0mS |
10.0mS |
1/2 cycle |
1/2 cycle |
| Max. Turn-off Time |
40.0mS |
40.0mS |
1/2 cycle |
1/2 cycle |
| Max.I²t for fusing (8.3mS) |
6000 |
6000 |
6000 |
6000 |
| Max. Off-State Leakage Current [mArms] |
10 |
5 |
10 |
5 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
| Control Voltage Range |
90-280Vrms |
90-280Vrms |
3-32Vdc |
3-32Vdc |
| Max. Turn-on Voltage |
90Vrms |
90Vrms |
3.0Vdc |
3.0Vdc |
| Min. Turn-off Voltage |
10Vrms |
10Vrms |
1.0Vdc |
1.0Vdc |
| Nominal Input Impedance [Ohms] |
60K |
60K |
See Note * |
See Note * |
| Typical Input Current |
2mA @ 120Vrms, 4mA @ 240Vrms |
2.0 mA * |
| * Input circuitry incorporates active current limiter. |
|
|
|
Power Controller to 70A
- K Series |
|
Features:
- Solid State Relay Assemblies rated to
70 A/pole @ 40° C (100% duty cycle)
- Available in 1, & 2 Pole configurations
- Relays approved to the following: UL,
CSA, VDE and CE
- Zero cross switching standard
- Phase angle - time proportioning control
optional
- Finger safe cover standard |
| OUTPUT SPECIFICATIONS |
AC |
DC |
| |
HBC- |
HBC- |
HBC- |
HBC- |
HBC- |
HBC- |
| |
90HAXK |
690HAXK |
125HAXK |
90HDXK |
690HDXK |
125HDXK |
| Operating Voltage (47-63 Hz) [Vrms] |
48-530 |
48-660 |
48-530 |
48-530 |
48-660 |
48-530 |
| Load Current Range [Arms] |
.04-60 |
.04-60 |
.04-70 |
.04-60 |
.04-60 |
.04-70 |
| Transient Overvoltage [Vpk] |
1200 |
1200 |
1200 |
1200 |
1200 |
1200 |
| Max. Surge Current, (16.6ms) [Apk] |
1200 |
1200 |
1750 |
1200 |
1200 |
1750 |
| Max. On-State Voltage Drop [Vpk] |
1.7 |
1.7 |
1.7 |
1.7 |
1.7 |
1.7 |
| Max. Turn-on Time |
10.0mS |
10.0mS |
10.0mS |
1/2 cycle |
1/2 cycle |
10.0mS |
| Max. Turn-off Time |
40.0mS |
40.0mS |
40.0mS |
1/2 cycle |
1/2 cycle |
40.0mS |
| Max.I²t for fusing (8.3mS) |
6000 |
6000 |
12,700 |
6000 |
6000 |
12,700 |
| Max. Off-State Leakage Current [mArms] |
10 |
5 |
10 |
10 |
5 |
10 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
| Control Voltage Range |
90-280Vrms |
90-280Vrms |
90-280Vrms |
3-32Vdc |
3-32Vdc |
3-32Vdc |
| Max. Turn-on Voltage |
90Vrms |
90Vrms |
90Vrms |
3.0Vdc |
3.0Vdc |
3.0Vdc |
| Min. Turn-off Voltage |
10Vrms |
10Vrms |
10Vrms |
1.0Vdc |
1.0Vdc |
1.0Vdc |
| Nominal Input Impedance [Ohms] |
60K Ohms |
60K Ohms |
60K Ohms |
See Note * |
See Note * |
1500 ** |
| Typical Input Current |
2mA @ 120Vrms, 4mA @ 240Vrms |
2.0 mA * |
2.0 mA * |
3.4mA @ 5Vdc, 20mA @ 28Vdc ** |
| * Input circuitry incorporates active current limiter. |
| ** Input circuitry for 480V models incorporates active current limiter with 2mA typical input current. |
|
|
|
Power Controller to 40A
- 3 Phase K Series |
|
Features:
- Solid State Relay Assemblies rated to
40 A/pole @ 40° C (100% duty cycle)
- Available in 2, & 3 Pole configurations
- Relays approved to the following: UL,
CSA, VDE and CE
- Zero cross switching standard
- Two or three legs controlled
- Voltage transient protection standard on
3 leg models
- LED standard on 3 leg models
- Finger safe cover standard |
| OUTPUT SPECIFICATIONS |
AC Control |
DC Control |
| |
HBC-T50AK |
HBC-90HAK-2 |
HBC-T50DK |
HBC-90HDK-2 |
| |
3 Phase / 3 Pole |
3 Phase / 2 Pole |
3 Phase / 3 Pole |
3 Phase / 2 Pole |
| Operating Voltage (47-63 Hz) [Vrms] |
48-530 |
48-530 |
48-530 |
48-530 |
| Load Current Range [Arms] |
0.1-30 / pole |
0.1-40 / pole |
0.1-30 / pole |
0.1-40 / pole |
| Transient Overvoltage [Vpk] |
1200 |
1200 |
1200 |
1200 |
| Max. Surge Current, (16.6ms) [Apk] |
625 |
1200 |
625 |
1200 |
| Max. On-State Voltage Drop [Vpk] |
1.6 |
1.7 |
1.6 |
1.7 |
| Max. Turn-on Time |
10.0mS |
10.0mS |
1/2 cycle |
1/2 cycle |
| Max. Turn-off Time |
40.0mS |
40.0mS |
1/2 cycle |
1/2 cycle |
| Max.I²t for fusing (8.3mS) |
1620 |
6000 |
1620 |
6000 |
| Max. Off-State Leakage Current [mArms] |
10 |
10 |
10 |
10 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
| Control Voltage Range |
90-280Vrms (60Hz) |
90-280Vrms (60Hz) |
3-32Vdc |
3-32Vdc |
| Max. Turn-on Voltage |
90Vrms |
90Vrms |
3.0Vdc |
3.0Vdc |
| Min. Turn-off Voltage |
10Vrms |
10Vrms |
1.0Vdc |
1.0Vdc |
| Nominal Input Impedance [Ohms] |
54.8K |
60K |
450 |
See * |
| Typical Input Current |
2.2mA @ 120Vrms, 4.4mA @ 240Vrms |
2mA @ 120Vrms, 4mA @ 240Vrms |
10mA @ 5Vdc |
2.0mA * |
| * Input circuitry incorporates active current limiter. |
|
|
|
Power Controller to 80A
- N Series |
|
Features:
- Solid State Relay Assemblies rated to
80A/pole @ 40° C (100% duty cycle)
- Available in 1 & 2 Pole configurations
- Relays approved to the following: UL,
CSA, VDE and CE
- Zero cross switching standard
- Finger safe cover standard
- Phase angle & time proportioning control optional |
| OUTPUT SPECIFICATIONS |
AC Control |
| |
HBC-50AN |
HBC-50HAN |
HBC-90HAN |
HBC-125HAN |
| Operating Voltage (47-63 Hz) [Vrms] |
24-280 |
48-530 |
48-530 |
48-530 |
| Load Current Range [Arms] |
.04-45 |
.04-45 |
.04-70 |
.04-80 |
| Transient Overvoltage [Vpk] |
600 |
1200 |
1200 |
1200 |
| Max. Surge Current, (16.6ms) [Apk] |
625 |
625 |
1200 |
1750 |
| Max. On-State Voltage Drop [Vpk] |
1.6 |
1.7 |
1.7 |
1.7 |
| Max. Turn-on Time |
10.0mS |
10.0mS |
10.0mS |
10.0mS |
| Max. Turn-off Time |
40.0mS |
40.0mS |
40.0mS |
40.0mS |
| Max.I²t for fusing (8.3mS) [A²sec] |
1620 |
1620 |
6000 |
12,700 |
| Max. Off-State Leakage Current [mArms] |
10 |
10 |
10 |
10 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
| Control Voltage Range |
90-280Vrms |
90-280Vrms |
90-280Vrms |
90-280Vrms |
| Max. Turn-on Voltage |
90Vrms |
90Vrms |
90Vrms |
90Vrms |
| Min. Turn-off Voltage |
10Vrms |
10Vrms |
10Vrms |
10Vrms |
| Nominal Input Impedance |
60K Ohms |
60K Ohms |
60K Ohms |
60K Ohms |
| Typical Input Current |
2mA @ 120Vrms, 4mA @ 240Vrms |
|
| OUTPUT SPECIFICATIONS |
DC Control |
| |
HBC-50DN |
HBC-50HDN |
HBC-90HDN |
HBC-125HDN |
| Operating Voltage (47-63 Hz) [Vrms] |
24-280 |
48-530 |
48-530 |
48-530 |
| Load Current Range [Arms] |
.04-45 |
.04-45 |
.04-70 |
.04-80 |
| Transient Overvoltage [Vpk] |
600 |
1200 |
1200 |
1200 |
| Max. Surge Current, (16.6ms) [Apk] |
625 |
625 |
1200 |
1750 |
| Max. On-State Voltage Drop [Vpk] |
1.6 |
1.7 |
1.7 |
1.7 |
| Max. Turn-on Time |
1/2 cycle |
1/2 cycle |
1/2 cycle |
1/2 cycle |
| Max. Turn-off Time |
1/2 cycle |
1/2 cycle |
1/2 cycle |
1/2 cycle |
| Max.I²t for fusing (8.3mS) [A²sec] |
1620 |
1620 |
6000 |
12,700 |
| Max. Off-State Leakage Current [mArms] |
10 |
10 |
10 |
10 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
| Control Voltage Range |
3-32Vdc |
3-32Vdc |
3-32Vdc |
3-32Vdc |
| Max. Turn-on Voltage |
3.0Vdc |
3.0Vdc |
3.0Vdc |
3.0Vdc |
| Min. Turn-off Voltage |
1.0Vdc |
1.0Vdc |
1.0Vdc |
1.0Vdc |
| Nominal Input Impedance |
1500 Ohms |
See Note * |
See Note * |
1500 ** |
| Typical Input Current |
3.4mA @ 5Vdc, 20mA @ 28Vdc |
2.0 mA * |
2.0 mA * |
3.4mA @ 5Vdc, 20mA @ 28Vdc ** |
| *Input circuitry incorporates active current limiter |
| ** Input circuitry for 480V models incorporates active current limiter with 2mA typical input current. |
|
|
|
Power Controller to 100A
- G Series |
|
Features:
- Solid State Relay Assemblies rated to
100A/pole @ 40° C (100% duty cycle)
- Available in 1, 2, & 3 Pole configurations
- Relays approved to the following: UL,
CSA, VDE and CE
- Zero cross switching standard
- Panel mount & finger safe cover standard
- Phase angle & time proportioning control optional |
| INPUT SPECIFICATIONS |
AC |
DC |
Part # |
HBC-90HAG |
HBC-690HAG |
HBC-125HAG |
HBC-90HDG |
HBC-690HDG |
HBC-125HDG |
| Control Voltage Range |
90-280Vrms |
90-280Vrms |
90-280Vrms |
3-32Vdc |
3-32Vdc |
3-32Vdc |
| Max. Turn-on Voltage |
90Vrms |
90Vrms |
90Vrms |
3.0Vdc |
3.0Vdc |
3.0Vdc |
| Min. Turn-off Voltage |
10Vrms |
10Vrms |
10Vrms |
1.0Vdc |
1.0Vdc |
1.0Vdc |
| Nominal Input Impedance [Ohms] |
60K |
60K |
60K Ohms |
See Note * |
See Note * |
See Note * |
| Typical Input Current |
2mA @ 120Vrms, 4mA @ 240Vrms |
2.0 mA * |
2.0 mA * |
3.4mA @ 5Vdc, 20mA @ 28Vdc ** |
| |
|
|
|
|
|
|
| OUTPUT SPECIFICATIONS |
|
|
|
|
|
|
| Operating Voltage (47-63 Hz) [Vrms] |
48-530 |
48-660 |
48-530 |
48-530 |
48-660 |
48-530 |
| Load Current Range [Arms] |
.04-80 |
.04-80 |
.04-100 |
.04-80 |
.04-80 |
.04-100 |
| Transient Overvoltage [Vpk] |
1200 |
1200 |
1200 |
1200 |
1200 |
1200 |
| Max. Surge Current, (16.6ms) [Apk] |
1200 |
1200 |
1750 |
1200 |
1200 |
1750 |
| Max. On-State Voltage Drop [Vpk] |
1.7 |
1.7 |
1.7 |
1.7 |
1.7 |
1.7 |
| Max. Turn-on Time |
10.0mS |
10.0mS |
10.0mS |
1/2 cycle |
1/2 cycle |
1/2 cycle |
| Max. Turn-off Time |
40.0mS |
40.0mS |
40.0mS |
1/2 cycle |
1/2 cycle |
1/2 cycle |
| Max.I²t for fusing (8.3mS) |
6000 |
6000 |
12,700 |
6000 |
6000 |
12,700 |
| Max. Off-State Leakage Current [mArms] |
10 |
5 |
10 |
10 |
5 |
10 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
0.5 |
|
|
|
Power Controller to 80A
- F Series |
|
Features:
- Solid State Relay Assemblies rated to
80A/pole @ 40° C (100% duty cycle)
- Replaces 80A 3 pole mercury contactors
- Zero cross switching standard
- Ball bearing fan standard; 50/60 hz
- 90° C over-temp cutout switch standard
- Relays & Fan: UL,
CSA, VDE and CE
- Transient voltage supression standard
- 600VAC available |
| OUTPUT SPECIFICATIONS |
AC Control |
DC Control |
| |
HBC-90AF2 |
HBC-90AF3 |
HBC-90DF2 |
HBC-90DF3 |
| |
|
|
| FAN OPTION (Add letter of Fan to end of above part #) |
B-120VAC Fan |
C - 240VAC Fan |
I - 24VDC Fan |
| (EX: HBC-90AF2B - Denotes 3 Phase, 2 Pole, w/120VAC Fan) |
| |
|
|
| |
3 Phase / 2 Pole |
3 Phase / 3 Pole |
3 Phase / 2 Pole |
3 Phase / 3 Pole |
| Operating Voltage (47-63 Hz) [Vrms] |
48-530 |
48-530 |
48-530 |
48-530 |
| Load Current Range [Arms] |
.04-80 |
.04-80 |
.04-80 |
.04-80 |
| Transient Overvoltage [Vpk] |
1200 |
1200 |
1200 |
1200 |
| Max. Surge Current, (16.6ms) [Apk] |
1200 |
1200 |
1200 |
1200 |
| Max. On-State Voltage Drop [Vpk] |
1.7 |
1.7 |
1.7 |
1.7 |
| Max. Turn-on Time |
10.0mS |
10.0mS |
1/2 cycle |
1/2 cycle |
| Max. Turn-off Time |
40.0mS |
40.0mS |
1/2 cycle |
1/2 cycle |
| Max.I²t for fusing (8.3mS) |
6000 |
6000 |
12700 |
12700 |
| Max. Off-State Leakage Current [mArms] |
10 |
10 |
10 |
10 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
| Control Voltage Range |
90-280Vrms (60Hz) |
3-32Vdc |
| Max. Turn-on Voltage |
90Vrms |
3.0Vdc |
| Min. Turn-off Voltage |
10Vrms |
1.0Vdc |
| Nominal Input Impedance [Ohms] |
60K |
See * |
| Typical Input Current |
2.2mA @ 120Vrms, 4.4mA @ 240Vrms |
2.0mA * |
| * Input circuitry incorporates active current limiter |
|
|
|
Power Controller to 100A
- F Series |
|
Features:
- Solid State Relay Assemblies rated to
100 A/pole @ 40° C (100% duty cycle)
- Replaces 100A 3 pole mercury contactors
- Zero cross switching standard
- Ball bearing fan standard; 50/60 hz
- 90° C over-temp cutout switch standard
- Relays & Fan: UL,
CSA, VDE and CE
- Transient voltage supression standard
- 600VAC available |
| OUTPUT SPECIFICATIONS |
AC Control |
DC Control |
| |
HBC-125AF2 |
HBC-125AF3 |
HBC-125DF2 |
HBC-125DF3 |
| |
|
|
| FAN OPTION (Add letter of Fan to end of above part #) |
B-120VAC Fan |
C - 240VAC Fan |
I - 24VDC Fan |
| (EX: HBC-125AF2B - Denotes 3 Phase, 2 Pole, w/120VAC Fan) |
| |
|
|
| |
3 Phase / 2 Pole |
3 Phase / 3 Pole |
3 Phase / 2 Pole |
3 Phase / 3 Pole |
| Operating Voltage (47-63 Hz) [Vrms] |
48-530 |
48-530 |
48-530 |
48-530 |
| Load Current Range [Arms] |
.04-100 |
.04-100 |
.04-100 |
.04-100 |
| Transient Overvoltage [Vpk] |
1200 |
1200 |
1200 |
1200 |
| Max. Surge Current, (16.6ms) [Apk] |
1750 |
1750 |
1750 |
1750 |
| Max. On-State Voltage Drop [Vpk] |
1.7 |
1.7 |
1.7 |
1.7 |
| Max. Turn-on Time |
10.0mS |
10.0mS |
1/2 cycle |
1/2 cycle |
| Max. Turn-off Time |
40.0mS |
40.0mS |
1/2 cycle |
1/2 cycle |
| Max.I²t for fusing (8.3mS) |
12700 |
12700 |
12700 |
12700 |
| Max. Off-State Leakage Current [mArms] |
10 |
10 |
10 |
10 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
| Control Voltage Range |
90-280Vrms (60Hz) |
3-32Vdc |
| Max. Turn-on Voltage |
90Vrms |
3.0Vdc |
| Min. Turn-off Voltage |
10Vrms |
1.0Vdc |
| Nominal Input Impedance [Ohms] |
60K |
See * |
| Typical Input Current |
2.2mA @ 120Vrms, 4.4mA @ 240Vrms |
2.0mA * |
| * Input circuitry incorporates active current limiter |
|
|
|
Dual Power Controller to 40A
- Dual Series |
|
Features:
- Solid State Relay Assemblies rated to
40A @ 40° C (100% duty cycle)
- Two independent AC Relays in one package
- Available in 2, 4, & 6Pole configurations
- Zero voltage switching standard
- Standard relays approved to the following: UL,
CSA, and CE
- Fast-on terminals standard |
| OUTPUT SPECIFICATIONS |
DC |
| |
HBC-D40HDA |
HBC-D40HEA |
| Operating Voltage (47-63 Hz) [Vrms] |
48-530 |
48-530 |
| Load Current Range [Arms] |
.15-40 / pole (40A total) |
.15-40 / pole (40A total) |
| Transient Overvoltage [Vpk] |
1200 |
1200 |
| Max. Surge Current, (16.6ms) (Apk) |
625 |
625 |
| Max. On-State Voltage Drop [Vpk] |
1.6 |
1.6 |
| Max. Turn-on and Turn-off Time |
1/2 cycle |
1/2 cycle |
| Max.I²t for fusing (8.3mS) |
1620 |
1620 |
| Max. Off-State Leakage Current [mArms] |
10 |
10 |
| Power Factor (Min.) with Max. Load |
0.5 |
0.5 |
| INPUT SPECIFICATIONS |
|
| Control Voltage Range [Vdc] |
4-15 |
4-15 |
| Max. Turn-on Voltage [Vdc] |
4.0 |
4.0 |
| Min. Turn-off Voltage [Vdc] |
1.0 |
1.0 |
| Nominal Input Impedance [Ohms] |
240 |
240 |
| Typical Input Current |
13mA @ 5Vdc |
13ma @ 24Vdc |
|
|
|