Strip Wire

30 Amp/Pole, 55 Amp/Pole, 70 Amp/Pole, 60 Amp/Pole, 60 Amp/Pole CMF

Strip Wire Power Controller to 70A - Strip Wire Series

Features:
- Solid State Relay Assemblies rated to 80 A/pole @ 40° C (100% duty cycle)

- Available in 1, 2 & 3 Pole configurations

- Relays approved to the following: UL, CSA, VDE and CE

- Zero cross switching standard

- LED status indicator standard

- Box clamp terminals with finger protection

INPUT SPECIFICATIONS AC Control
 
HBC-650CHAA
HBC-690CHAA
HBC-690CHAL
HBC-690CHAXK
HBC-690CHAN
HBC-690CHAK-2
          3 Phase / 2 Pole
Control Voltage Range [Vrms]
90-280
90-280
90-280
90-280
90-280
90-280
Max. Turn-on Voltage [Vrms]
90
90
90
90
90
90
Min. Turn-off Voltage [Vrms]
10
10
10
10
10
10
Typical Input Current 15mA @ 120Vrms
 
INPUT SPECIFICATIONS DC Control
 
HBC-650CHDA
HBC-690CHDA
HBC-690CHDL
HBC-690CHXDK
HBC-690CHDN
HBC-690CHDK-2
3 Phase / 2 Pole
Control Voltage Range [Vdc]
4-32
4-32
4-32
4-32
4-32
4-32
Max. Turn-on Voltage [Vdc]
4.0
4.0
4.0
4.0
4.0
4.0
Min. Turn-off Voltage [Vdc]
1.0
1.0
1.0
1.0
1.0
1.0
Max. Input Current (Active current limited)
30
30
30
30
30
30
Typical Input Current 14mA @ 5Vdc
 
OUTPUT SPECIFICATIONS  
Operating Voltage  (47-63 Hz) [Vrms]
48-660
48-660
48-660
48-660
48-660
48-660
Load Current Range [Arms]
.04-30
.04-40
.04-50
.04-60
.04-70
.04-40/pole
Transient Overvoltage [Vpk]
1200
1200
1200
1200
1200
1200
Max. Surge Current, (16.6ms) (Apk)
625
1200
1200
1200
1200
1200
Max. On-State Voltage Drop  [Vpk]
1.7
1.7
1.7
1.7
1.7
1.7
Max. Turn-on and Turn-off Time
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
1/2 cycle
Max.I²t for fusing  (8.3mS)
1620
6000
6000
6000
6000
6000
Max. Off-State Leakage Current [mArms]
1.0
1.0
1.0
1.0
1.0
1.0
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
0.5
0.5
Strip Wire Power Controller to 60A - CMF Series

Features:
- Solid State Relay Assemblies rated to 60 A/pole @ 40° C (100% duty cycle)

- Available in 1, 2, & 3 Pole configurations

- Relays approved to the following: UL, CSA, VDE and CE

- Zero cross switching standard

- LED status indicator & DIN mount standard

- Box clamp terminals with finger protection

- 12 VDC Fan Included

INPUT SPECIFICATIONS
AC Control
DC Control
 
HBC-690CHAA-I
HBC-690CHDA-I
Control Voltage Range
90-280Vrms
4-32Vdc
Max. Turn-on Voltage
90Vrms
4Vdc
Min. Turn-off Voltage
10Vrms
1Vdc
Typical Input Current
15mA @ 120Vrms
14mA @ 5 Vdc
 
OUTPUT SPECIFICATIONS  
Operating Voltage  (47-63 Hz) [Vrms]
48-660
48-660
Load Current Range [Arms]
.04-60
.04-60
Transient Overvoltage [Vpk]
1200
1200
Max. Surge Current, (16.6ms) [Apk]
1200
1200
Max. On-State Voltage Drop  [Vpk]
1.7
1.7
Max. Turn-on Time
10.0
1/2 cycle
Max. Turn-off Time
40.0
1/2 cycle
Max.I²t for fusing  (8.3mS)
6000
6000
Max. Off-State Leakage Current [mArms]
1.0
1.0
Power Factor  (Min.) with Max. Load
0.5
0.5
Power Controller to 55A - T75 Series

Features:
- Solid State Relay Assemblies rated to 55 A/pole @ 40° C (100% duty cycle)

- 3 Pole, 3 Phase configuration

- Relay approved to the following: UL, CSA, VDE and CE

- Zero cross switching standard

- Strip Wire termination

- Higher power available with fan option

- Internal SSR Over-Temp sensor optional

- Over temp snap switch optional

INPUT SPECIFICATIONS
AC Control
DC Control
 
HBC-T75AG
HBC-T75DG
Control Voltage Range
24-275Vac (24-50Vdc)
4-32Vdc
Max. Turn-on Voltage
18Vac (20Vdc)
3.8Vdc
Min. Turn-off Voltage
9Vac/dc
1.2Vdc
Typical Input Current
15mA
23mA
 
OUTPUT SPECIFICATIONS  
Operating Voltage  (47-65 Hz) [Vrms]
42-660
42-660
Load Current Range [Arms]
.15-55
.15-55
Transient Overvoltage [Vpk]
1200
1200
Max. Surge Current, (10ms) [Apk]
1150
1150
Max. On-State Voltage Drop  [Vpk]
1.6
1.6
Max. Turn-on Time [mS]
20.0
10
Max. Turn-off Time [mS]
30.0
10
Max.I²t for fusing  (8.3mS)
6600
6600
Max. Off-State Leakage Current [mArms]
3
1.0
ALARM OUTPUT SPECIFICATIONS  
Collector - Emitter Voltage [Vdc]
35
35
Emitter - Collector Voltage [Vdc]
6
6
Collector Current [mA]
50
50
Delay time on Reset [mS]
20
20
Power Controller to 30A - HK Series

Features:
- Solid State Relay Assemblies rated to 30 A/pole @ 40° C (100% duty cycle)

- Relays approved to the following: UL, CSA, VDE and CE

- LED status indicator standard

- Zero cross switching standard

- Ground terminals included

- Strip Wire Connections

- Intergraded Heatsinks

- Finger-safe Terminals

OUTPUT SPECIFICATIONS AC DC
 
HKA4830-1
HKA4830-2
HKA4830-3
HKD4830-1
HKD4830-2
HKD4830-3
Single Phase
3 Phase / 2 Pole
3 Phase / 2 Pole
Single Phase
3 Phase / 2 Pole
3 Phase / 2 Pole
Operating Voltage  (47-63 Hz) [Vrms]
48-530
48-530
48-530
48-530
48-530
48-530
Load Current Range [Arms]
.15-30
.15-30/pole
.15-30/pole
.15-30
.15-30/pole
.15-30/pole
Transient Overvoltage [Vpk]
1200
1200
1200
1200
1200
1200
Max. Surge Current, (16.6ms) (Apk)
625
625
625
625
625
625
Max. On-State Voltage Drop  [Vpk]
1.6
1.6
1.6
1.6
1.6
1.6
Max. Turn-on Time
10.0mS
10.0mS
10.0mS
1/2 cycle
1/2 cycle
1/2 cycle
Max. Turn-off Time
40.0mS
40.0mS
40.0mS
1/2 cycle
1/2 cycle
1/2 cycle
Max.I²t for fusing  (8.3mS)
1620
1620
1620
1620
1620
1620
Max. Off-State Leakage Current
10
10
10
10
10
10
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
0.5
0.5
INPUT SPECIFICATIONS  
Control Voltage Range 90-280Vrms 4.5-32Vdc
Max. Turn-on Voltage 90Vrms 4.5Vdc
Min. Turn-off Voltage 10Vrms 1.0Vdc
Typical Input Current
2mA @ 120Vrms, 4 mA @ 240Vrms
15mA @ 12Vdc, 20mA @ 24Vdc
Power Controller to 30A - HK60 Series

Features:
- Solid State Relay Assemblies rated to 30 A/pole @ 25 ° C (100% duty cycle)

- Relays approved to the following: UL, CSA, VDE and CE

- LED status indicator & DIN mount standard

- Zero cross switching standard

- Ground terminals included

- Strip Wire Connections

- Intergraded Heatsinks

- Finger-safe Terminals

INPUT SPECIFICATIONS
AC
DC
 
Single Phase
3 Phase / 2 Pole
3 Phase / 2 Pole
Single Phase
3 Phase / 2 Pole
3 Phase / 2 Pole
HKA6030-1
HKA6030-2
HKA6030-3
HKD6030-1
HKD6030-2
HKD6030-3
Control Voltage Range
90-280Vrms
4.5-32Vdc
Max. Turn-on Voltage
90Vrms
4.5Vdc
Min. Turn-off Voltage
10Vrms
1.0Vdc
Typical Input Current
2mA @ 120Vrms, 4 mA @ 240Vrms
15mA @ 12Vdc, 20mA @ 24Vdc
OUTPUT SPECIFICATIONS
Operating Voltage  (47-63 Hz) [Vrms]
48-660
48-660
48-660
48-660
48-660
48-660
Load Current Range [Arms]
.15-30
.15-30/pole
.15-30/pole
.15-30
.15-30/pole
.15-30/pole
Transient Overvoltage [Vpk]
1200
1200
1200
1200
1200
1200
Max. Surge Current, (16.6ms) (Apk)
625
625
625
625
625
625
Max. On-State Voltage Drop  [Vpk]
1.6
1.6
1.6
1.6
1.6
1.6
Max. Turn-on Time
10.0mS
10.0mS
10.0mS
1/2 cycle
1/2 cycle
1/2 cycle
Max. Turn-off Time
40.0mS
40.0mS
40.0mS
1/2 cycle
1/2 cycle
1/2 cycle
Max.I²t for fusing  (8.3mS)
1620
1620
1620
1620
1620
1620
Max. Off-State Leakage Current
10
10
10
10
10
10
Power Factor  (Min.) with Max. Load
0.5
0.5
0.5
0.5
0.5
0.5
 

Home Distributors New Products Relays Contacts RequestsInformation